Page text
Sheet
Drawing No.
HILTI, Inc.
Tulsa, Oklahoma USA (800) 879-8000
Date
Scale
2. PENETRATING ITEM TO BE ONE OF THE FOLLOWING (ALSO SEE NOTE NO. 3 BELOW) :
A. MAXIMUM 6" NOMINAL DIAMETER PVC PLASTIC PIPE (CELLULAR OR SOLID CORE).
B. MAXIMUM 6" NOMINAL DIAMETER CPVC PLASTIC PIPE (SDR 11 OR SDR 13.5) (CLOSED PIPING
SYSTEM ONLY).
C. MAXIMUM 6" NOMINAL DIAMETER ABS PLASTIC PIPE (CELLULAR OR SOLID CORE).
D. MAXIMUM 6" NOMINAL DIAMETER FRPP PLASTIC PIPE.
E. MAXIMUM 6" NOMINAL DIAMETER AQUARISE CPVC PLASTIC PIPE (SDR 11) MANUFACTURED BY IPEX,
INC. (CLOSED PIPING SYSTEM ONLY).
F. MAXIMUM 6" NOMINAL DIAMETER XFR 15/50 PVC PIPE (CELLULAR OR SOLID CORE).
G. MAXIMUM 4" NOMINAL DIAMETER RIGID NONMETALLIC CONDUIT (SCH 40 PVC).
3. MINIMUM 1/2" DEPTH HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT.
4. HILTI CP 643N FIRESTOP COLLAR WITH FASTENING HOOKS (SEE TABLE BELOW).
5. EACH FASTENING HOOK SECURED TO BOTTOM OF FLOOR WITH 1/4" x 1-3/4" LONG STEEL EXPANSION
BOLTS OR STEEL CONCRETE SCREW ANCHORS IN CONJUNCTION WITH 3/4" DIAMETER STEEL WASHERS,
OR 0.145" DIAMETER x 1-1/4" LONG POWDER ACTUATED FASTENERS IN CONJUNCTION WITH 1-7/16"
DIAMETER STEEL WASHERS (EX. HILTI KWIK-BOLT 3, KWIK-CON, OR DX PINS).
NOTES : 1. HILTI CP 643N FIRESTOP COLLARS AND FS-ONE FIRESTOP SEALANT ARE REQUIRED ON BOTH
SIDES OF A WALL ASSEMBLY.
2. MINIMUM ANNULAR SPACE = 0".
3. CLOSED OR VENTED PIPING SYSTEM (PVC, ABS, FRPP, AND XFR-PVC = SCHEDULE 40; CPVC =
SDR 11 OR 13.5).
4. FT RATINGS ARE 1-HR AND 2-HR FOR 2-HR AND 3-HR FIRE-RATED ASSEMBLY, RESPECTIVELY.
cUL
2 of 2
-
cUL SYSTEM NO. C-AJ-2035
PLASTIC PIPE THROUGH CONCRETE FLOOR/WALL OR BLOCK WALL
CANADA ONLY
NOMINAL PIPE
DIAMETER
PRODUCT DESCRIPTION
NO. OF FASTENING
HOOKS
MAXIMUM HOLE
SIZE
MAXIMUM
ANNULAR SPACE
1-1/2"
CP 643 50/1.5" N
2
OJNLU?
3/16"
2"
CP 643 63/2" N
2
OJRLU?
1/4"
3"
CP 643 90/3" N
3
4"
1/2"
4"
CP 643 110/4" N
3
5"
1/2"
6"
CP 643 160/6" N
4
7"
1/2"
Dec. 11, 2012
cUL CAJ2035h.121112
F-RATING = 2-HR. OR 3-HR.
FT-RATING = 1-HR. OR 2-HR.
FH AND FTH-RATINGS = 0-HR.
L-RATING AT AMBIENT = LESS THAN 1 CFM / SQ FT
L-RATING AT 400° F = LESS THAN 1 CFM / SQ FT
NOTE : TESTED WITH A 50 Pa PRESSURE DIFFERENTIAL