Page text
Sheet
Drawing No.
HILTI, Inc.
Tulsa, Oklahoma USA (800) 879-8000
Date
Scale
NOTES : 1. MAXIMUM DIAMETER OF OPENING = 5-3/4".
2. ANNULAR SPACE = MINIMUM 0", MAXIMUM 7/8".
1. CONCRETE WALL ASSEMBLY (1-HR., 2-HR., 3-HR., OR 4-HR. FIRE-RATING) :
A. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE WALL (MINIMUM 6" THICK).
B. ANY UL/cUL CLASSIFIED CONCRETE BLOCK WALL.
2. PENETRATING ITEM TO BE ONE OF THE FOLLOWING :
A. MAXIMUM 4" NOMINAL DIAMETER STEEL PIPE (SCHEDULE 10 OR HEAVIER).
B. MAXIMUM 4" NOMINAL DIAMETER CAST IRON PIPE.
C. MAXIMUM 4" NOMINAL DIAMETER COPPER PIPE.
D. MAXIMUM 4" NOMINAL DIAMETER STEEL CONDUIT OR EMT.
3. HILTI FIRESTOP SEALANT APPLIED PER TABLE BELOW.
4. MINIMUM 1/2" HILTI BEAD OF FIRESTOP SEALANT APPLIED AT POINT OF CONTACT.
WJ
NOOS~
1 of 1
1/8" = 1"
June 12, 2012
UL/cUL SYSTEM NO. W-J-1226
tgNOOS~KMSNONO
F-RATING = 1-HR., 2-HR., 3-HR., OR 4-HR.
T-RATING = 0-HR.
L-RATING AT AMBIENT = LESS THAN 1 CFM/SQ FT
L-RATING AT 400° F = 4 CFM/SQ FT
METAL PIPE THROUGH CONCRETE WALL OR BLOCK WALL ASSEMBLY
F, FH RATINGS HR.
SEALANT TYPE
SEALANT THICKNESS, IN.
1, 2
FS-ONE OR CP 606
5/8
3
FS-ONE OR CP 606
1
4
FS-ONE
1
A
SECTION A-A
FRONT VIEW
A
1
2
3
4