/ 1699
WJ 1128a — page 175

Page text

Sheet
Drawing No.
HILTI, Inc.
Tulsa, Oklahoma USA (800) 879-8000
Date
Scale
A
NOTES : 1. MAXIMUM DIAMETER OF OPENING = 31-7/8".
2. ANNULAR SPACE = MINIMUM 0", MAXIMUM 1-7/8".
1. CONCRETE WALL ASSEMBLY (2-HR. FIRE-RATING) :
A. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE WALL (MINIMUM 5" THICK).
B. ANY UL/cUL CLASSIFIED CONCRETE BLOCK WALL.
2. PENETRATING ITEM TO BE ONE OF THE FOLLOWING :
A. MAXIMUM 30" NOMINAL DIAMETER STEEL PIPE (SCHEDULE 40 OR HEAVIER).
B. MAXIMUM 30" NOMINAL DIAMETER CAST IRON PIPE.
C. MAXIMUM 6" NOMINAL DIAMETER COPPER PIPE.
D. MAXIMUM 6" NOMINAL DIAMETER STEEL CONDUIT.
E. MAXIMUM 4" NOMINAL DIAMETER EMT.
3. MINIMUM 1-1/4" DEPTH HILTI CP 606 FLEXIBLE FIRESTOP SEALANT.
4. MINIMUM 1/2" BEAD HILTI CP 606 FLEXIBLE FIRESTOP SEALANT APPLIED AT POINT OF CONTACT.
WJ
1128b
1 of 1
9/64" = 1"
Aug. 19, 2010
UL/cUL SYSTEM NO. W-J-1128
WJ1128b.081910
F-RATING = 2-HR.
T-RATING = 0-HR.
L-RATING AT AMBIENT = LESS THAN 1 CFM/SQ. FT.
L-RATING AT 400°F = LESS THAN 1 CFM/SQ. FT.
METAL PIPE THROUGH CONCRETE WALL OR BLOCK WALL ASSEMBLY
SECTION A-A
FRONT VIEW
A
1
2
3
4